|
A
large percentage of our transformers are used in rectifiers
of the type illustrated in Figure 1, so we decided to
dedicate this first edition of TRANSFORMER FACTS to
rectifier transformers, and provide some practical tips
for power supply designers.
| "The
AC current supplied to a rectifier always equals
the DC current drawn from the rectifier when
leakage currents in the diodes can be ignored."
Q:
True or False?
A: True and False.
|
The
opening statement is true if we compare average currents
(Im) on both the AC and the DC side of the
rectifier. But AC current is always measured as average
current (IRMS), while DC current is always
measured as average current (Im). The opening
statement is false if we compare IRMS on
the AC side with Im on the DC side of the
rectifier.
The
RMS current (IRMS) is always larger than
the average current (Im) because of the peaked
shape of the AC current. When IRMS is divided
by Im we obtain a measure of the peakedness
of the current, which is called Form Factor. (F = IRMS/Im).
The sharper the peaks are, the larger is the value of
F.
The
heating effect of an electrical current in wiring, resistors,
and transformer windings is proportional to the square
of the RMS current. The heating effect of the AC current
in a rectifier circuit is accordingly proportional to
ISœ = (F‡Im)œ
= (F‡IL )œ, or the square
of the DC current multiplied by F squared. The
temperature rise in a given rectifier transformer is
thus heavily dependent of the value of the Form Factor
(F), and the required size of a rectifier transformer
cannot be determined until the actual value of the Form
Factor is known.
In
a rectifier of the type shown in Figure 1, F has a value
somewhere between 1.11 and 5.0 depending on the relative
values of the impedances before and after the diode
bridge. When these impedances are known, it is possible
to calculate F (and UC) using graphical methods
published by Schrade
in 1943. But at that point the power supply designer
usually has in his hand a prototype transformer, so
UC and IS can be determined quickly
by bench tests. (Be careful to measure IS
with a meter measuring true RMS current. Most AC current
meters measure Im but are graduated in IRMS,
assuming F=1.11 which is only true for sinewave.
An
accurate and simple method for determining the Form
Factor (F) from oscilloscope readings with the aid of
graphs developed by Toroid Corporation of Maryland is
described below.
Let
us assume we observe the current and voltage waveforms
in different parts of the circuit of Figure 1 on a CRT
oscilloscope, so we can compare waveforms before and
after the diode bridge. Diagrams I-III show oscillograms
for different values of the capacitor (C), assuming
a transformer with negligible series inductance, such
as a toroidal transformer.
The
desired effect of the capacitor is to smooth the DC
voltage, but at the same time it causes the AC current
to flow in short bursts, which means higher F and larger
RMS current in the transformer. The "conduction
angle" (a) of the rectifier can be measured directly
off the oscillogram - just remember that a full halfcycle
is 180þ.
It
is clear that the Form Factor (F) must depend on the
conduction angle (a). We have calculated the exact relationship
between F and a for toroidal transformers, and the result
is shown here in this graph. By measuring the conduction
angle (a) off the oscilloscope a very accurate value
for the Form Factor (F) can be read off the graph. Variations
in DC load will change the conduction angle, and the
corresponding changes in the Form Factor can easily
be determined.
The
graph sheet includes more information, which can serve
as an aid to evaluating the trade-offs in power supply
design. In the comments to the diagrams we have defined
h=UDC/Ço, which relates the DC
voltage to the peak no-load voltage of the transformer
secondary. The flattening of the tops of the AC voltage
waveform is caused by the voltage drop in the total
impedance ahead of the diode bridge, so it is reasonable
to assume that h must vary with the conduction angle
(a). We have calculated this relationship also, again
assuming toroidal transformers, and the result is shown
in the graph sheet enclosed as a broken curve.
An
important use of the graph for h is to determine the
DC load regulation of a rectifier. DC load regulation
DUDC/UDC = (1-h) ‡ 100%. Remember
that the diode voltage drops are included in the valued
for UDC. Each diode voltage drop can be assumed
to be constant = 1V at all loads. The net load regulation
is accordingly slightly worse than 1-h, especially for
low DC voltages.
It
is important to note that better efficiency of voltage
conversion (as measured by h) can only be obtained at
the cost of higher Form Factor, and conversely lower
Form Factor can only be obtained at the cost of poorer
DC load regulation.
The
size of the transformer supplying the rectifier is proportional
to the product of no-load voltage (Uo) and
current capacity (IS), which we call Po.
The dotted line in the graph sheet represents the lowest
value of Po required for any value of a (of
any corresponding value of F or h) for a given DC power.
(Po/PDC = F/‹2).
The
transformer has a minimum size (Po) of about
1.52 ‡ PDC (total DC power including diode
losses) for a = 75þ, where h= .8 and F = 1.7. Unfortunately
it is not possible to stay near the minimum at all times,
partly because better DC regulation than 20% is often
required, and partly because the load regulation of
transformers vary widely with transformer size. DC load
regulation and transformer load regulation are not proportional,
but they generally increase and decrease together, so
very small transformers tend to work at larger than
optimal values of a, and very large transformers work
at smaller than optimal values of a.
The
design of a rectifier transformer to meet specific requirements
for U, U, DC regulation, temperature rise, etc., requires
exact data for both Form Factor (F) and rectification
efficiency (h). But F and hare in turn determined by
the data of the not-yet-designed transformer, so the
power supply designer is caught in a "Catch-22"
situation. One way out is to grab some old design, modify
it some, and pray that the prototype will work.
Another
way out is to let Toroid Corporation of Maryland do
the transformer design. Our application engineers have
solid backgrounds in transformer and power supply design,
and they have at their disposal interactive computer
programs for transformer optimization, so they can design
not only a transformer that will work, but also the
most economical transformer that will do the job.

 |
Comments: |
| IL=
¡
‡ œ/p (average) |
| IS
= ¡
‡ 1/‹2 (RMS) |
| F
= IS/IL= p/(2
‡ ‹2) = 1.1107 |
Diagram
I.
C = 0. No regulator |
 |
Comments: |
| UDC
=
UC +
UDIODES |
| UDC/Ço
=
h=
h(a) |
| a
=
conduction angle |
| F
= IS/IL= f (a) |
Diagram
II.
C ’ Æ |
 |
Comments: |
| Ripple
Voltage (Ur) Symmetrical on UC |
| UDC
to center of slope - otherwise as in II. |
Diagram
III.
C = normal (Ur /UC<10%).
Regulator working |
O.H. Schrade: "Analysis
of Rectifier Operation" Proceedings of the I.R.E.,
July 1943, pp.341-361. (This paper is difficult to find
even in libraries. The important parts of the graphs
are reprinted in MOTOROLA Silicon Rectifier Manual.)
|